ONICON Incorporated 727-447-6140
Page 42
www.onicon.com
SYSTEM-20 BTU METER
30251
User Defined Volume Total - Mode 2 - m3
Input Register
Floating Point Register (1 of 2)
30252
User Defined Volume Total - Mode 2 - m3
Input Register
Floating Point Register (2 of 2)
30253
Auxiliary Pulse Input Count- Input 1
Input Register
Floating Point Register (1 of 2)
Unitless count. Value is representative
of the total number of pulses received
on input.
30254
Auxiliary Pulse Input Count- Input 1
Input Register
Floating Point Register (2 of 2)
Unitless count. Value is representative
of the total number of pulses received
on input.
30255
Auxiliary Pulse Input Count- Input 2
Input Register
Floating Point Register (1 of 2)
Unitless count. Value is representative
of the total number of pulses received
on input.
30256
Auxiliary Pulse Input Count- Input 2
Input Register
Floating Point Register (2 of 2)
Unitless count. Value is representative
of the total number of pulses received
on input.
30257
Auxiliary Pulse Input Count- Input 3
Input Register
Floating Point Register (1 of 2)
Unitless count. Value is representative
of the total number of pulses received
on input.
30258
Auxiliary Pulse Input Count- Input 3
Input Register
Floating Point Register (2 of 2)
Unitless count. Value is representative
of the total number of pulses received
on input.
30259
Run Hours
Input Register
Floating Point Register (1 of 2)
30260
Run Hours
Input Register
Floating Point Register (2 of 2)
30261
Meter Status
Input Register
Short Integer Register
0 Normal
1 Low Supply Temperature
2 High Supply Temperature
3 Low Return Temperature
4 High Return Temperature
5 Delta T < Minimum
6 High Energy Rate
7 Low Signal Quality
8 Comm Error
9 Low Supply Voltage
10 System Fault