SYSTEM-20 BTU METER
1.4 ADDITIONAL REQUIRED
HARDWARE
The System-20 must be connected to a suitable volumetric flow meter and a
matched pair of temperature sensors in order to calculate and report heat data.
Please refer to ONICON’s flow meter literature, or contact ONICON for help in
selecting the flow meter that will best fit your requirements.
Flow Meter Model
Line Sizes
Straight Run
Required
Notes
F-1100 Single Turbine Insertion Flow Meter
1 ¼" and larger
25
Can be used in 1"
copper lines
F-1200 Dual Turbine Insertion Flow Meter
2 ½" and larger
15
F-11XX Inline Turbine Flow Meter
¾" and 1"
25
F-3500 Insertion Electromagnetic Flow Meter
1 ¼" and larger
See manual
FT-3100 and F-3200 Inline Electromagnetic Flow Meters
¼" and larger
5
F-4300 Clamp-on Ultrasonic Flow Meter
2" and larger
See manual
F-4600 Inline Ultrasonic Flow Meter
½" - 2 ½"
See manual
Temperature/Sensors
ONICON Standard Temperature Sensors (32°F – 200° F)
Pair of solid state temperature sensors with 0 – 20 mA outputs. Suitable for use
with fluid temperatures up to 200° F.
Platinum RTD Temperature Sensors (32°F – 250° F)
Pair of 4-wire 1000 Ω Platinum RTD temperature sensors. Suitable for use with
fluid temperatures up to 250° F.
Please refer to ONICON’s System-20 product literature, or contact ONICON for
help in selecting the temperature sensors and thermowells that will best fit your
requirements.
The System-20 was designed for installation and use in typical domestic and
commercial environments that are free of corrosive liquids and fumes, direct
liquid exposure, temperature extremes and vibrations.
The operating ambient air temperature range is -13°F to 140° F. The electrical
power should be relatively clean, free of high frequency noise, large voltage
transients, and protected from power surges and brown outs.
CAUTION (5)
The System-20 battery cannot be retrofitted or replaced. Risk of fire
explosion, and burns. DO NOT recharge, disassemble, crush, heat above
212°F (100°C) or incinerate. Please check your local ordinances for
information concerning battery disposal.
IMPORTANT NOTE (6)
The System-20 may be installed outdoors in protected spaces away from
direct sunlight, rain, sleet or snow.
1.5 WORKING ENVIRONMENT