- 14 -
2.
Position and way of connection, refer to figure 15.
3.
Output power cable is designed according to load current, do not use
over-thin cable. Please refer to Table 2
Model Max.
output current
Output cable
Terminal specification
Online UPS PP1KL
4A
12AWG
5.5~6
Online UPS PP2KL
8A
10AWG
5.5~6
Online UPS PP3KL
12A
10AWG
5.5~6
Online UPS PP4KL
16A
10AWG
5.5~6
Online UPS PP5KL
20A
10AWG
5.5~6
Online UPS PP6KL
24A
10AWG
5.5~6
Online UPS PP8KL
32A
8AWG
8.5~9
Online UPS PP10KL
40A
8AWG
8.5~9
Online UPS PP12KL
48A
8AWG
8.5~9
Online UPS PP15KL
60A
5AWG
16~9
Table 2
4.
Avoid short-circuit and overload.
5.
The comparison between output current rating and output cable size is
listed in Table 2.
6.
The ground to this unit only acts as reference point, if the ground isn’t
good, that may cause disturbance and false datum management, and
affect UPS and computer, please ask professional personnel for handling
immediately.
7.
User offers a good grounding system.
8.
Try to make the ground close to connecting point of grounding club or