- 35 -
Model
Online
UPS
PP1KL
Online
UPS
PP2KL
Online
UPS
PP3KL
Online
UPS
PP4KL
Online
UPS
PP5KL
Online
UPS
PP6KL
Online
UPS
PP8KL
Online
UPS
PP10KL
Online
UPS
PP12KL
Online
UPS
PP15KL
Internal protection equipment LCD panel
Battery
UPS automatically shutdowns when battery is low power level, there is no fuse switch
protection.
Overload
When load reaches 110~150% of rating, transfer to bypass after 3s, recover auto.
Over-temperat
ure
Automatically transfer to bypass if UPS internal temperature > 85
℃
Output
short-circuit
Limit current, automatic shutdown, fuse and there no fuse switch protection.
UPS abnormal
Automatically transfer to bypass and supplied power by utility
Noise filter
10~100KHz at 40Db; 100KHz~100MHz at 70dB
LCD display
input, output voltage, frequency, battery voltage, output power (%), temperature
Battery BVL
One LED, it lit on when battery low voltage
Environment
Temperature 0~40
℃
Humidity 20~90%
non-condensing
Noise
<58dB (1m away from enclosure)
General
Output socket
Terminal plate
Unit weight
(no battery)
46Kg 55Kg
60Kg
65Kg
67Kg 69Kg 105Kg 115Kg 135Kg 220
Kg
Dimension
(mm)
W×D×H
230×580×720 305×585×864
409×798
×1044
Others
Full efficiency
>85%
Transform
time
when utility
fault
0s
UPS status
indicator light
Utility, inverter, bypass, UPS abnormal (fault)
Communicatio
n interface
RS232 interface