C O M M U N I C A T I O N
104 / 192
XS20000_31_manual_ger_eng_it_V1.1.2.doc
R. Kistler
6.1
Communication options
The XANTO S features a serial (RS-232) and a USB communica-
tions port as well as two slots for optional interface cards.
NOTE
The data transfer rate of the USB interface (USB 1.1) is set
to 2400 baud.
6.1.1
RS-232 and USB communication interfaces
To facilitate communication between the UPS system and a comput-
er, connect the computer using a suitable data cable (RS-232 cable,
included in the scope of supply) to one of the communication ports of
the UPS. Figure 26 shows the position of the communication ports.
HINWEIS
RS-232 and USB communication interface cannot be used
simultaneously.
When the connection cable is connected, the DataWatch software
can exchange data with the UPS system (see "
DataWatch soft-
ware
“). The software calls up detailed specifications about the status
of the power supply environment from the UPS system. If an emer-
gency power situation becomes necessary, the software will trigger
the storage of all data and a proper shutdown of the system.
The assignment of the cable connection pins for the RS-232 com-
munications port is shown in Figure 27; refer to Table 9 for the func-
tions of the connection pins.
Figure 27: RS-232 communication port (DB-9 connector)
Summary of Contents for 10000 3/1 XANTO S Series
Page 2: ...2 192 XS10000 XS20000_31_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Page 64: ...64 192 XS10000 XS20000_31_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Page 66: ...66 192 XS10000 XS20000_31_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Page 128: ...128 192 XS10000 XS20000_31_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Page 130: ...130 192 XS10000 XS20000_31_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Page 192: ...192 192 XS10000 XS20000_31_manual_ger_eng_it_V1 1 2 doc R Kistler ...