C O M M U N I C A T I O N
105 / 192
XS20000_31_manual_ger_eng_it_V1.1.2.doc
R. Kistler
Pin
Function
Input / Output
2
Transmission data (TxD)
Output
3
Receive data (RxD)
Input
5
Ground
Table 9: Connection assignment of the RS-232
6.1.2
Slots for interface cards
The XANTO S is equipped with two slots (see Figure 26) for the fol-
lowing interface cards:
Intelligent slot
Art. no.
Description
DW7SNMP30
SNMP Adapter Basic
The SNMP adapter communicates via TCP/IP with the connected
consumers in the network.
DW5SNMP30
SNMP Adapter Professional
Function like basic, however, with additional interface for tempera-
ture sensor and building management.
Table 10: Interface cards, slot 1
AS400 slot
Art. no.
Description
PHXNOV-I
Relay module
Message from battery mode, normal mode and battery capacity
low.
Signal input for UPS shutdown.
PHXAS400I
AS400 interface
Message from UPS alarm, bypass active, battery voltage low,
inverter inoperable and power failure.
Signal input for UPS shutdown.
Table 11: Interface cards, slot 2