6.1.3 Emergency-off function (REPO)
The emergency-off function (REPO = Remote Emergency Power-
Off) serves to shut down the UPS system and to immediately switch
off the connected consumers remotely. The REPO connector
(rear side of the UPS system) must be removed and an external
emergency-off switch must be connected for this.
Connection cable cross-section = 0.32 - 4mm
2
(AWG 22 - 12)
Recommended connection cable cross-section = 1.5mm
2
(AWG 18)
CAUTION
The emergency-off switch may not be connected to circuits
that are connected with the mains power supply network.
A reinforced insulation to the mains is required. The emer-
gency-off switch must be dimensioned for at least 24V and
20mA. An opening contact must be used. For proper opera-
tion, the emergency-off function must remain active for at
least 250ms
If the emergency-off function is activated, the input voltage of
the UPS system must additionally be disconnected
NOTE
Leave the REPO connector in the emergency-off connector
plugged into the UPS system if the emergency-off function is
not required
Always test the emergency-off function before a critical load
is connected. This will prevent an unintended load breaking
Summary of Contents for ONLINE XANTO S 1000
Page 2: ...2 222 XS700 XS3000_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Page 74: ...74 222 XS700 XS3000_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Page 76: ...76 222 XS700 XS3000_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Page 148: ...148 222 XS700 XS3000_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Page 150: ...150 222 XS700 XS3000_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Page 222: ...222 222 XS700 XS3000_manual_ger_eng_it_V1 1 2 doc R Kistler ...