M A I N T E N A N C E
131 / 222
XS700-XS3000_manual_ger_eng_it_V1.1.2.doc
...........................................................
R. Kistler
Figure 19: Typical installation of multiple battery modules
6. Inserting the front cover of the battery module. To insert the
cover again, make sure that the cables of the battery module
are guided through the cable ejections. Then slide the cover to
the right until it engages in the holder on the right side of the
housing. Reattach the two screws on the right side of the front
cover. Repeat the procedure for each additional battery mod-
ule.
7. Make sure that the complete wiring and all plug connections of
the UPS system as well as the battery modules lie behind the
front cover and are not accessible to the user.
7.5 Testing the new batteries
1. Connect the UPS system to the mains power for 48 hours to
charge up the batteries.
2. Press any button to activate the menu options. Select
"CONTROL" and then "START BATTERY TEST".
The UPS system starts a battery test when the batteries are
completely charged, the UPS system is in normal mode with-
out active warning messages and the bypass voltage is ac-
ceptable.
During the battery test, the UPS system switches to battery
mode and discharges the batteries for 25 seconds. The " Bat-
tery test running
" together with the progress in percent is
shown on the control panel.
Summary of Contents for ONLINE XANTO S 1000
Page 2: ...2 222 XS700 XS3000_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Page 74: ...74 222 XS700 XS3000_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Page 76: ...76 222 XS700 XS3000_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Page 148: ...148 222 XS700 XS3000_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Page 150: ...150 222 XS700 XS3000_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Page 222: ...222 222 XS700 XS3000_manual_ger_eng_it_V1 1 2 doc R Kistler ...