T E C H N I C A L D A T A
140 / 222
XS700-XS3000_manual_ger_eng_it_V1.1.2.doc
...........................................................
R. Kistler
9.1.3 Electrical inputs and outputs
Nominal frequency
50 / 60Hz automatic detection
Frequency range
40 - 70 Hz before switching to battery mode
Bypass voltage range
+10 / -15% of the nominal voltage (standard)
Overvoltage protection
MOVs for normal and common
overvoltage’s
Table 14: Input power
Model
Line input
Voltage/
current
Selectable output
voltages
Voltage range at
100% load
XANTO S 700
XANTO S 700R
230 V /
3.0A
200V, 208V,
220V, 230V, 240V
160 - 276VAC
XANTO S 1000
XANTO S 1000R
230 V /
4.3A
200V, 208V,
220V, 230V, 240V
160 - 276VAC
XANTO S 1500
XANTO S 1500R
230 V /
6.5A
200V, 208V,
220V, 230V, 240V
160 - 276VAC
XANTO S 2000
XANTO S 2000R
230 V /
8.7A
200V, 208V,
220V, 230V, 240V
180 - 276VAC
XANTO S 3000
XANTO S 3000R
230 V /
13.0A
200V, 208V,
220V, 230V, 240V
180 - 276VAC
Table 15: Electrical input and output power
Model
Input connection
Output connections
XANTO S 700
XANTO S 700R
IEC320 C14
6x IEC320 C13
XANTO S 1000
XANTO S 1000R
IEC320 C14
6x IEC320 C13
XANTO S 1500
XANTO S 1500R
IEC320 C14
6x IEC320 C13
XANTO S 2000
XANTO S 2000R
IEC320 C14
8x IEC320 C13
1x IEC320 C19
XANTO S 3000
XANTO S 3000R
IEC320 C20
8x IEC320 C13
1x IEC320 C19
Table 16: Electrical input and output connections
Summary of Contents for ONLINE XANTO S 1000
Page 2: ...2 222 XS700 XS3000_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Page 74: ...74 222 XS700 XS3000_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Page 76: ...76 222 XS700 XS3000_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Page 148: ...148 222 XS700 XS3000_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Page 150: ...150 222 XS700 XS3000_manual_ger_eng_it_V1 1 2 doc R Kistler ...
Page 222: ...222 222 XS700 XS3000_manual_ger_eng_it_V1 1 2 doc R Kistler ...