INSTALLATION
14 / 56
X700-3000_usermanual_engl_20170405.docx
DC Input” cover on the last battery pack. Keep the covers and
the screws.
2. Connect all plug connections between the battery packs and the
UPS system. This involves connecting the “VDC Output” output
on a battery pack with the “VDC Input” on the upstream battery
pack. The battery pack connected directly to the UPS system is
connected to the “VDC Input” on the UPS system. A maximum
of seven battery packs can be connected to the UPS system.
3. Enter the number of battery packs used in menu no. 7 (see
Chapter 4.3
Settings
).
4. Continue the getting started process (see Chap. 3.6)
3.6 Getting started
PLEASE NOTE
Make sure that the overall rated performance of the load con-
nected does not exceed the capacity of the UPS system. The
power consumption of inductive loads or laser printers can be
very high, please take this into consideration when specifying
your UPS system.
1. If you install additional battery packs, make sure they are
properly connected (see Chap. 3.4, 3.5) and the battery fuse on
the back of the battery packs is switched on.
2. Connect the load with the UPS system without switching them
on. Make sure that the UPS system has two groups of output
sockets. The programmable output sockets can be switched in-
dependently of the remaining sockets. The programmable out-
put sockets are primarily designed for less critical load which
cannot be brought down using software. Critical load should not
be connected to the programmable output sockets.
3. Connect the power supply cable (supplied with the XANTO
2000 and 3000) for the UPS system into a socket. The display
on the UPS system shows “Sb”,
4. Hold the “ON / / ” button on the UPS system down until you
hear a short beep.