MAINTENANCE
36 / 56
X700-3000_usermanual_engl_20170405.docx
CAUTION
DANGER OF ELECTRIC SHOCK. Never make changes to
the battery cabling or connections. Attempting to change the
battery cabling yourself could lead to serious injury.
The batteries of the UPS system are very heavy. Be careful
when handling heavy batteries.
6.5 Changing the batteries in rack
PLEASE NOTE
Do not replace the batteries while the UPS system is in battery
mode.
The hot-swap functionality means the batteries can be replaced with-
out shutting down the UPS system and disconnecting the load.
If you would prefer to disconnect the UPS system before changing the
batteries, read Chapter 3.6
Getting started
.
CAUTION
Maintenance work must be carried out by a qualified techni-
cian who is familiar with batteries and the necessary safety
measures. Do not allow unauthorised personnel to handle the
batteries.
Batteries pose the risk of an electric shock or injury due to high
short circuit current. Take the following safety measures:
o
remove watches, jewellery and other metal items
o
only use tools with insulated handles
o
do not place tools or metal components on the batteries
The batteries must only be replaced with the same number of
batteries of the same type.
Batteries must be properly disposed of. When disposing of
batteries, comply with the statutory regulations applicable in
your location.
Batteries must not be burnt. There is risk of explosion.