3. Electrical installation
CAUTION
• The UPS system carries life-threatening voltages. All repair and maintenance work
must be carried out by customer service personnel.
• Always connect the earth conductor first.
• Comply with regional legislation and rules on connecting electrical devices.
Table 2: Recommended cable cross sections
Description
XANTO
6000
XANTO
10000
XANTO
10000 3/1
XANTO
20000 3/1
Input
6mm
2
10mm
2
10mm
2
16mm
2
Output
6mm
2
10mmv
10mm
2
16mm
2
Earth conductor
6mm
2
10mmv
10mm
2
16mm
2
Connection fittings
M5
M5
M5
M6
Cable lug, external max.
10mm
10mm
12mm
18mm
Fuse in battery pack
50A
50A
100A
100A
Remove the cover of the terminal strip and connect the cables as shown in the diagrams below:
Figure 1: XANTO 6000 / 10000 terminal strip
Figure 2: XANTO 10000 3/1 terminal strip
Figure 3: XANTO 20000 3/1 terminal strip
Safety information and quick start guide UPS XANTO
•