O P E R A T I O N
56 / 120
ZE1000-3000_manual_ger_eng_it_V1.0.3
........................................................................
R. Kistler
String
Description
STbY
UPS system in standby mode
IPVL
Line input voltage too low
IPVH
Line input voltage too high
IPFL
Line input frequency too low
IPFH
Line input frequency too high
NORM
UPS system in normal mode
AVR
UPS system in normal mode
Additional buck-boost function
bATT
UPS system in normal mode
TEST
Function or battery test in progress
OPVH
Line output voltage too high
OPVL
Line output voltage too low
OPST
Short circuit at output of the UPS system
OVLD
Overload at output of the UPS system
bATH
Battery voltage too high
bATL
Battery voltage too low
OVTP
Internal temperature too high
FNLK
Fan blocked
bTWK
Batteries weak
Table 4: Operating status overview
4.3
Settings
1. Select the settings mode: Keep the button
pressed for 3
seconds.
2. Scroll between the settings: Press the button until the de-
sired setting appears (see Table 5).
3. Select setting: Keep the button
pressed for 1 second. The
setting now flashes.
4. Change setting: Press the button until the desired setting
appears (see Table 5).
5. Confirm setting: Keep the button
pressed for 1 second.
6. Exit setup mode: Keep the button
pressed for 3 seconds.
Summary of Contents for XANTO E 1000
Page 2: ...2 120 ZE1000 3000_manual_ger_eng_it_V1 0 3 R Kistler ...
Page 39: ...39 120 ZE1000 3000_manual_ger_eng_it_V1 0 3 R Kistler ...
Page 40: ...40 120 ZE1000 3000_manual_ger_eng_it_V1 0 3 R Kistler ...
Page 42: ...42 120 ZE1000 3000_manual_ger_eng_it_V1 0 3 R Kistler ...
Page 79: ...79 120 ZE1000 3000_manual_ger_eng_it_V1 0 3 R Kistler ...
Page 80: ...80 120 ZE1000 3000_manual_ger_eng_it_V1 0 3 R Kistler ...
Page 82: ...82 120 ZE1000 3000_manual_ger_eng_it_V1 0 3 R Kistler ...
Page 119: ...119 120 ZE1000 3000_manual_ger_eng_it_V1 0 3 R Kistler ...
Page 120: ...120 120 ZE1000 3000_manual_ger_eng_it_V1 0 3 R Kistler ...