M A I N T E N A N C E
69 / 120
ZE1000-3000_manual_ger_eng_it_V1.0.3
........................................................................
R. Kistler
5. Replace the batteries in the battery module insert.
NOTE
Check whether the replacement batteries have the same
specifications as the old batteries.
Please read the "
Disposing of old batteries or the UPS sys-
tem
" section for information on proper disposal.
6. Install the battery module insert in reverse order.
CAUTION
A small spark can occur when the batteries are connected to
the UPS system. This is normal and does not pose a hazard
to people. Quickly and firmly insert the cable of the batteries
into the battery plug connection of the UPS system.
7. Proceed with section
Testing the new batteries
.
6.5
Testing the new batteries
1. Connect the UPS system to the mains power for 48 hours to
charge up the batteries.
2. Press the button for
10 seconds to start the battery test.
"TEST" appears in the display.
3. When the batteries are defective, a warning message appears
automatically (see Table 4).
NOTE
The UPS system starts a battery test only when the batteries
are completely charged and the UPS system is in normal
mode without active warning messages.
Summary of Contents for XANTO E 1000
Page 2: ...2 120 ZE1000 3000_manual_ger_eng_it_V1 0 3 R Kistler ...
Page 39: ...39 120 ZE1000 3000_manual_ger_eng_it_V1 0 3 R Kistler ...
Page 40: ...40 120 ZE1000 3000_manual_ger_eng_it_V1 0 3 R Kistler ...
Page 42: ...42 120 ZE1000 3000_manual_ger_eng_it_V1 0 3 R Kistler ...
Page 79: ...79 120 ZE1000 3000_manual_ger_eng_it_V1 0 3 R Kistler ...
Page 80: ...80 120 ZE1000 3000_manual_ger_eng_it_V1 0 3 R Kistler ...
Page 82: ...82 120 ZE1000 3000_manual_ger_eng_it_V1 0 3 R Kistler ...
Page 119: ...119 120 ZE1000 3000_manual_ger_eng_it_V1 0 3 R Kistler ...
Page 120: ...120 120 ZE1000 3000_manual_ger_eng_it_V1 0 3 R Kistler ...