Seite 57 von 128
Specific LED and audible signal combinations indicate certain
statuses, as shown below (see also Section 10.5):
Mode
LED combination
Audible
signal
1
2
3
4
5
Al
a
rm
Li
ne
By
pa
ss
Invert
er
B
a
tter
y
0 – 25%
z
z
z
None
26 – 50%
z
z
z
z
None
51 – 75%
z
z
z
z
z
None
76 – 100%
z
z
z
z
z
z
None
101 – 105%
z
z
z
z
z
z
z
None
No
rm
al
mo
de
(l
o
a
d
)
> 105%
z
z
z
z
z
z
z
2x
/
sec.
0 – 25%
z
z
z
1x / sec.
26 – 50%
z
z
z
z
1x / 3 sec.
51 – 75%
z
z
z
z
z
1x / 3 sec.
76 – 95%
z
z
z
z
z
z
1x / 3 sec.
Ba
ttery mode
(ca
-
pa
city)
>96%
z
z
z
z
z
z
z
1x / 3 sec.
Short
circuit
z
z
}
}
Continuous
Charger
fault
z
z
}
}
Continuous
Overtemperature
z
z
}
}
Continuous
Fan fault
z
z
}
}
}
}
1x / sec.
Rectifier fault
z
z
}
}
Continuous
Inverter
fault
z
}
}
Ï
Continuous
Overload
z
z
z
z
z
z
}
}
Continuous
Battery faulty (normal
mode)
}
}
}
}
}
z
z
Ï
None
Battery fault
(standby mode)
}
}
}
}
}
}
Ï
None
No battery
}
}
}
}
}
z
}
Ï
6x
z
= ON
}
= Dependent upon other operating status
Ï
= Flashing
Table 3: Fault codes (LED and audible signal combinations)