Seite 81 von 128
AUTONOMY TIME
Minutes (at 50% / 100% effective power load)
Standard (internal battery)
17 / 6
-
-
+ 1 Batterypack
-
18 / 6
12 / 5
+ 2 Batteriepacks
-
51 / 19
31 / 16
+ 3 Batteriepacks
-
93 / 36
55 / 26
+ 4 Batteriepacks
-
121 / 53
73 / 40
INTERFACE, SOFTWARE
RS-232 interface
Yes
Dry contacts (battery capac-
ity high/low, shutdown)
Yes
Network management card,
basic
Optional
Network management card,
professional
Optional
USB-adaptor Optional
DataWatch software
Included in scope of supply
Table 12: Electrical specifications
11.3 Ambient conditions
MODEL
XANTO RT
1000
XANTO RT
2000
XANTO RT
3000
Operating temperature (°C)
0 - 40
Storage temperature (°C)
-25 to +55
Relative humidity (%)
5 - 95%, no condensation
Cooling
Active cooling, 2 internal fans, air inlet on
front
Altitude
1500 - 3000m, power derating of 1% per
additional 100m
Operating noise (dB)
43
45
45
Table 13: Ambient conditions