M A I N T E N A N C E
123 / 216
XS10000_manual_ger_eng_it_V1.1.2.doc
R. Kistler
7.
Maintenance
7.1
Care and maintenance of UPS systems
/batteries
To ensure a long service life of the system, the area around the UPS
system should be kept clean and free of dust. If the area around the
system is very dusty, cleaning the outer surfaces of the system using
a vacuum cleaner.
To ensure a long service life of the batteries, the ambient tempera-
ture should lie below 25°C.
NOTE
The batteries of the UPS system are designed for a service
life of 3 to 5 years. However, the service life of a battery var-
ies depending on the frequency of use and ambient tempera-
ture. After expiration of the expected service life, batteries
which continue to be used frequently have reduced running
times. Replace the batteries every five years at the latest so
that the system can provide optimal power at any time.