I N S T A L L A T I O N
95 / 216
XS10000_manual_ger_eng_it_V1.1.2.doc
R. Kistler
3.6
Electrical installation
CAUTION
Always connect the protective earthing conductor first
Do not perform any unauthorised modifications to the UPS
system as doing otherwise will damage the system and void
the warranty
Only qualified electricians may connect the UPS system to
the power supply
3.6.1
Cable cross-sections and fuses
XANTO S 6000
XANTO S 10000
Line input
4mm
2
6mm
2
Output (Terminal)
4mm
2
6mm
2
Separate ground conductor
(only rack)
4mm
2
6mm
2
Circuit breaker 2-pole
in the feedline (not included)
32A
50A
Trigger characteristic C
Fuse in the battery module
60A
80A
Table 2: Cable cross-section (multicore) and fuses
3.6.2
Terminal strip
Please unscrew the two screws at the terminal cover (see Figure 12)
for access to the terminal strip.
Figure 12: Terminal cover XANTO S 6000 and 10000