User guide Automatic Transfer Switch 

 Page 13

Page 12 

 

User guide Automatic Transfer Switch

8    Trouble Shooting

Use the table below to solve minor problems.

Problem

Possible Cause

Solution

The ATS with the mains 
voltage present, 
does don’t turn on
(The LEDs does not flash 
and no alarm sounds)

No connection with input plugs

Connect the mains to the input plugs as indicated 
in the installation section.

Input switch in “OFF” position

Turn the input switches in “ON” position.

Input power failure

Check that the mains voltage is present or check 
if the UPS supplying the ATS is powered on.

Protective device upstream activated Reset the protective device. 

WARNING

 

Check that there is no overload or short-circuit at the 
output of the UPS.

The load is not powered

No connection with output sockets

Connect the load to the output sockets.

Intervention of 10A/16A thermal  
protection

The thermal protection device will operate in the event 
of a short circuit or overload on one of the 10A/16A 
output sockets. The thermal protection can be reset 
by pushing the button in which will result in the power 
being reconnected to the load. Therefore prior to 
attempting a reset of the thermal protection, please 
check the connected loads rating and/or determine if 
there are any problems. Then once reset, reconnect 
each load one at a time to ensure no problems exists.

The display shows 
nothing or provides 
incorrect information

There is power supply problem 
in display

Shut down the ATS completely and wait for a few  
seconds. Switch the ATS on again, if the problem per-
sists, contact the nearest technical support centre.

The display is off but 
the load is powered

There is power supply problem 
in display

Contact the nearest technical support centre.

If there is any abnormal situations occur, which doesn't list above, please call the service people immediately 
for professional examine.

9    Specifications

Model

ATS-30A

Input
Input Voltage

220/230/240 VAC

Acceptable Input Voltage Range

180 - 258 VAC 

Input Frequency

50 Hz/60 Hz 

Maximum Input Current

30 A

Output
Output Voltage

220/230/240 VAC

Maximum Output Current

10 A for IEC-C13 outlets
16 A for IEC-C19 outlet
30A for Grand connector

Connection
Input

2 x Grand connectors

Output

4 x IEC-C13 
1 x IEC-C19
1 x Grand

Communication

USB/RS-232

Charge current

USB/RS-232

Transfer time

8-12ms (Typical), 16ms max.

Physical
Dimension, D x W x H (mm)

330 x 483 x 44

Net Weight (kgs)

5

Environment
Operating Temperature

0-95 % RH @ -5°C- 45°C (non-condensing)

Summary of Contents for ATS-30A

Page 1: ...www online ups com USER MANUAL AUTOMATIC TRANSFER SWITCH Model ATS 30A ...

Page 2: ... Introduction 4 2 Product Overview 5 3 Safety Warnings 6 4 Operation Indicators Status 7 5 Installation 8 6 Operation 9 7 Communication Port 10 8 Trouble Shooting 12 9 Specifications 13 10 Appendix 14 Imprint 15 ...

Page 3: ...urce the ATS can also switch power back to the primary input when power to the primary input is restored Package contents ATS module User manual Mounting brackets Download from www online ups com 2 Product Overview Front View 1 Power switch for input source A 2 Power switch for input source B 3 Circuit breaker for output 2 4 Circuit breaker for output 3 5 USB communication port 6 RS 232 communicat...

Page 4: ...PLEASE NOTE These instructions may be modified by the wiring regulations in force in the country where the ATS is purchased 4 Operation Indicators Status 1 Source preference selector 2 Priority setting LEDs 3 Power source status LEDs 4 Output source LEDs 5 Fault indicator 6 Alarm mute button Indication type LED description LED status Condition Alarm Priority setting LEDs Source A 2 ON Source A is ...

Page 5: ...he terminal cover by removing four screws Step 2 Fasten the input output wirings through the cable gland Step 3 Fasten the terminal cover and cable gland to the unit Then customer can plug the user load to the output 10A Output 3 or 16A Output 2 sockets depending on user s requirements 6 Operation Power On Off Put the input power switch in ON position The output will then be supplied by the source...

Page 6: ...ee fig 1 which can be connected to an external monitoring system such as a BMS in order to monitor the operational status of the ATS The external equipment must respect the voltage and current characteristics of contacts port Focus on contacts port The contacts port provides the following pins Pin 1 common contact Pin 2 Source B active contact if the contact between pin 1 and pin 2 is closed outpu...

Page 7: ...or to attempting a reset of the thermal protection please check the connected loads rating and or determine if there are any problems Then once reset reconnect each load one at a time to ensure no problems exists The display shows nothing or provides incorrect information There is power supply problem in display Shut down the ATS completely and wait for a few seconds Switch the ATS on again if the...

Page 8: ...k to Source B Setting Source B as priority power source and Source A is powering Low point 190V High point 248V Acceptable input frequency for Source A Source A will be power source during this range When input frequency of source A is beyond this range ATS will automatically switch to power from Source B 45Hz 55Hz Acceptable input frequency for Source B Source B will be power source during this r...

Page 9: ...ONLINE USV Systeme AG Luise Ullrich Straße 8 DE 82031 Grünwald www online ups com ...

Reviews: