10 Appendix
Input Voltage and Frequency Thresholds
Function
Description
Default setting
Acceptable input voltage range
for Source A
Source A will be power source during this range.
When input voltage of source A is beyond this range,
ATS will automatically switch to power from Source B.
180V – 258V
Return voltage point
for Source A
When input voltage of Source A is back to normal,
the ATS will switch back to Source A. (Setting Source A
as priority power source and Source B is powering)
Low point: 190V
High point: 248V
Acceptable input voltage range
for Source B
Source B will be power source during this range.
When input voltage of source B is beyond this range,
ATS will automatically switch to power from Source A.
180V – 258V
Return voltage point
for Source A
When input voltage of Source B is back to normal,
the ATS will switch back to Source B. (Setting Source B
as priority power source and Source A is powering)
Low point: 190V
High point: 248V
Acceptable input frequency
for Source A
Source A will be power source during this range.
When input frequency of source A is beyond this range,
ATS will automatically switch to power from Source B.
45Hz – 55Hz
Acceptable input frequency
for Source B
Source B will be power source during this range.
When input frequency of source B is beyond this range,
ATS will automatically switch to power from Source A.
45Hz – 55Hz
ONLINE USV-Systeme AG
Luise-Ullrich-Straße 8
82031 Grünwald / Germany
Phone +49 (0)89-242 39 90-10
E-Mail info@online-usv.de
ONLINE USV-Systeme AG
c/o swizzconnexx
Pilatusstrasse 17
5630 Muri / Switzerland
Phone +41 (0)41-500 28 68
E-Mail info@online-usv.ch
ONLINE UPS-Systems S.r.l.
Via Ferruccio Gilera 110
20862 Arcore (MB) / Italia
Phone +39 (0)39-205 14 44
E-Mail commerciale@online-ups.it
Imprint
The content is copyright © 2022 by ONLINE USV-Systeme AG.
All rights reserved. Unauthorised reproduction in part or in whole is not permitted without consent.