OPERATION
20 / 42
Z800-3000_usermanual_engl_updated_202001.docx
Setting
Available options
Standard
Select output voltage:
[208] = 208V
[220] = 220V
[230] = 230V
[240] = 240V
“230V”
Programmable output sockets:
[ENA] = Enabled
[DIS] = Disabled
“DIS”
Shutdown time for programmable output
sockets:
[0 - 999] = Shutdown of programmable
output sockets in battery mode after time
defined here.
Only available if “Programmable output
sockets = active” and UPS system re-
started after setting the time.
“999”
Battery deep discharge protection:
Shutdown of all output sockets in battery
mode after time defined here.
[0
– 999] = Shutdown after 0 to 999
minutes.
[DIS] = Shutdown time dependent on bat-
tery capacity.
Attention: If the setting is [0], shutdown is
after 10 seconds.
“DIS”
Emergency power off function:
[AO] = active open, emergency power off
is active with emergency power off con-
tact open
[AC] = active close, emergency power off
is active with emergency power off con-
tact closed
“AO”
Exit:
Exiting configuration menu
Table 6: Configuration menu