background image

 

ENANCER Electrónica Lda

 

 

Página 3 de 3

 

Rua Max Grundig 9 

 

 

 

4705-820 Braga Portugal                                                                                                                                             info@only-smartbuildings.com                                     
Tel: +351 253 221 484                                                                                                                                                 www.only-smartbuildings.com 

2.  Select the desired input to modify the type using keys 1 to 4. 
The green led flashes the number of times according to the following table: 
 

1 - Push button 
2 - Detector normally closed (positive transition) 
3 - Detector normally open (negative transition) 

 
3.  Press PROG repeatedly until the desired type is selected. 
4.  Press key [1..4] to confirm and exit. 
 

Associating inputs to outputs 

 
To associate one of the module's inputs to an output, it is necessary to set an output in programming mode. To do 
this, proceed as follows: 
 
1.  Press shortly the PROG key in the D8OUT_4IN or in any other actuator. 
2.  The desired output(s) must now be selected. 
3.  In this module the selection is made on the respective key (1 to 8) 
4.  Press key 1, 2, 3 or 4 corresponding to the input you want to associate with the selected output (s) for 2 seconds. 
Release the key. 
5.  From this moment onwards, input 1 ,2, 3 or 4 will control the output(s) you selected. 
6.  Programming can be done for all desired outputs at once or one at a time. 
 
Note: 
If a module or command enters programming mode and exits again it will imply that the programming mode in all 
modules and commands in the installation will also be terminated. 
 

Enable/disable automatic sending of the status of the outputs 

 
To activate  or deactivate the automatic sending  to the bus of the status  when any output changes its status press 
button 8 for 5 seconds. 
 
Activated: All leds turn on briefly (300ms). 
Deactivated: All leds turn on for 1 second. 
 

Factory setting: 

 

1. Sending automatically the status indication to the bus is activated. 
2. The normally open contact (negative transition) is selected for all the 4 inputs. 
3. Toggle is selected for all the 4 inputs. 