Description optek Control 4000 / Haze Control bus interface
- 13 -
optek-Manual--1004-1010-02--ProfibusPA-US-2017-06-23
5.1
Technical data PROFIBUS
®
PA interface
Tab. 2
Technical data PROFIBUS
®
PA interface
Physical:
IEC 61158-2
31.25 kbit/s
voltage mode
Connection:
polarity-independent
Voltage range:
9…32 V
Background current:
18 mA
Galvanic separation:
function separation
Intrinsic safety:
no
ID:
0x0BF3
Address range:
3 to 126
delivery state 126
Set_Slave_Adr. of master
Device profile:
PROFIBUS
®
PA profile, version 3.01 with amendment 2
Block structure:
1 PB
4 AI with 1 TB each
4 DI with 1 TB
2 AO with 1 TB
1 status TB (device-specific)