- 31 -
optek-Manual--1004-1010-02--ProfibusPA-US-2017-06-23
Specifications
7.2
Analyzer TB for measuring results M01–M04
Note!
* slot 11: measuring result M01 = OUT_1_(mA)
slot 12: measuring result M02 = OUT_2_(mA)
slot 13: measuring result M03 = OUT_3_(mA)
slot 14: measuring result M04 = OUT_4_(mA)
Tab. 8
Analyzer TB for the four measuring results M01–M04
Rel. Index Slot index Parameter
Data type
Size
(bytes)
Access
0
16
BLOCK_OBJECT
DS-32
20
R
1 17
ST_REV
Unsigned16
2
R
2
18
TAG_DESC
Octet String
32
R, W
3 19
STRATEGY
Unsigned16
2
R,
W
4 20
ALERT_KEY
Unsigned8
1
R,
W
5
21
TARGET_MODE
Unsigned8
1
R, W
6
22
BLOCK_MODE
DS-37
3
R
7
23
ALARM_SUM
DS-42
8
R
8
24
COMPONENT_NAME
Octet String
32
R, W
9
25
PV
DS-60
12
R
PV
Floating point
4
MEASUREMENT_STATUS
Unsigned8
1
PV_TIME
Date
7
10
26
PV_UNIT
Unsigned16
2
R, W
11
27
PV_UNIT_TEXT
Octet String
8
R, W
12
28
ACTIVE_RANGE
Unsigned8
1
R, W
13
29
AUTORANGE_ON
Boolean
1
R, W
14
30
SAMPLING_RATE
Time_difference
4
R, W
25
41
NUMBER_OF_RANGES
Unsigned8
1
R
26
42
RANGE_1
DS-61
8
R, W
Begin_of_Range
Float
1
End_of_Range
Float
1
27
43
PRODUCT
Visible String
12
R
28
44
OUT_1_(mA)*
Float
4
R