2-10
2.4. 200KVA ~ 320KVA UPS 3-Phase Input / 3-Phase Output
TECHNICAL SPECIFICATION
KVA
200
240
300
320
RECTIFIER
INPUT VOLTAGE
220V
∆
/ 380V
∆
/ 460V
∆
, 208VY / 380VY
/ 400VY / 415VY
INPUT RANGE
307 – 520V
INPUT FREQUENCY
50 / 60 Hz +/- 7%
INPUT POWER FACTOR
0.8
NORMAL INPUT CURRENT(A)
350
420
525
560
MAXIMUM INPUT CURRENT(A)
437
525
656
700
POWER WALK IN
15% - 100% : 15 sec
EFFICIENCY
99%
VOLTAGE REGULATION
1%
CURRENT LIMIT(A)
525
630
788
840
RIPPLE VOLTAGE
0.5%
BATTERY
BATTERY TYPE
SEAL LEAD ACID / NiCd
NO. OF CELLS
174 / 271
VOLTAGE RANGE
295 – 410VDC / 285-415VDC
MAXIMUM CHARGE
CURRENT (ADC)
100
120
150
160
BATTERY LOW VOLTAGE
320VDC / 305VDC
BATTERY LOW STOP VOLTAGE
295VDC / 285VDC
BOOST CHARGE
410VDC / 415VDC
FLOAT CHARGE
396VDC / 410VDC