9-3
Abnormal
Description & Checkpoint
Solution
(6) Fans cannot
work while
UPS is on.
The fuses positioned behind PCB holder
have been blown or are not installed well.
Replace the fuses or install
them well.
Abnormal voltage output in R phase.
Refer to PCB LED
Detecting Guide and check
the 3T PCB of R phase.
(7) The
rectifier shunt
down and
HIGH DC LED
lit up.
Voltage limit function failure in the 3B,
which contributes to the DC voltage
becomes over 430V.
Refer to PCB LED
Detecting Guide and check
the 3B PCB.
3C PCB has problem.
Refer to PCB LED
Detecting Guide and check
the 3C PCB.
(8) Abnormal
voltage in
reserve.
RESERVE AC FAIL LED lights up. LCD
menu also displays the abnormal voltage
in reserve. (REAL TIME DATA menu
→
RESERVE DATA menu).
Check the reserve wiring
and connect with the right
source.
Fuse has blown in 3A PCB
Replace the fuse.
If the abnormal cannot be improved as the
aforesaid solution action has been taken.
Refer to PCB LED
Detecting Guide and check
the 3A PCB.
(9) Abnormal
frequency in
reserve.
RESERVE FREQ FAIL LED lights up.
LCD menu also displays the abnormal
voltage in reserve. (REAL TIME DATA
menu
→
RESERVE DATA menu).
Check the reserve wiring
and connect with the right
source.
Fuse has blown in 3A PCB
Replace the fuse.
If the abnormal cannot be improved as the
aforesaid solution action has been taken.
Refer to PCB LED
Detecting Guide and check
the 3A PCB.
Summary of Contents for DS-D33
Page 1: ...OPTI UPS User s Guide Durable Series Models DS D33 www opti ups com ...
Page 16: ...1 12 1 7 Dimension Drawings 20KVA 60KVA OUTLINE DRAWING ...
Page 17: ...1 13 20KVA 60KVA INTERIOR DRAWING ...
Page 18: ...1 14 80KVA 160KVA OUTLINE DRAWING ...
Page 19: ...1 15 80KVA 160KVA INTERIOR DRAWING ...
Page 20: ...1 16 200KVA 320KVA OUTLINE DRAWING ...
Page 21: ...1 17 200KVA 320KVA INTERIOR DRAWING ...
Page 22: ...1 18 INTER PCB DIAGRAM ...