Trouble Shooting
22
DS-I 1-3k UPS User Manual
components for batteries.
82
Output CT fault
Output CT assembled
mistakenly
Check if the output CT has been
assembled mistakenly. Assemble the
output CT as the device package on
PCB.
NOTICE
Please provide the following information when reporting fault UPS:
1)
The UPS model and serial NO.
2)
The warn and fault code happened
3)
Detail of fault, include LED indicates, buzzer beeps, power condition, load capacity
and configuration of battery(long backup time model)