5. INDICATION AND CONTROL

 

5.1 LED Display 
5.1.1 Battery level and load level LEDs 
The battery level LEDs show the voltage level both in back-up mode and in normal mode.  
When the LED indicates 20% of the capacity in back-up mode, it means that the UPS is going to 
shut down; for the length of backup time left, it will depend on the load.    While when all five 
LEDs are lighted in normal mode, it means that the battery is fully charged. 

The load level LEDs show the percentage of added load by the UPS’s rated capacity.    When all five 
LEDs are lighted, the UPS is over loaded.

 

5.1.2 Operation status LED 
The status LED shows the UPS status.  It shows Green when the utility power is normal; and shows 
Orange in the event of a utility outage; while if the UPS is under fault operation, it shows Red.

 

5.2 LCD Display 
5.2.1 Main control button: Please refer to point 4 & 5 (4.1~4.7 & 5.3~5.4). 

5.2.2 LCD screen 
 

 

 

 

 

 

 

 

Summary of Contents for Inverter Series

Page 1: ...0 www opti ups com Inverter Series User Manual IS1100LT IS2200LT IS3000LT IS5000LT IS2000LR IS2700LR IS4000LR IS5000LR 1100VA 5000VA ...

Page 2: ...y any individuals with no previous experience The socket outlet shall be installed near the equipment and easily accessible With the installation of this equipment it should be prevented that the sum of the leakage current of the INVERTER AND UPS at the connected consumer does not exceed 3 5mA Attention hazardous through electric shock Also with disconnection of this unit from the main hazardous v...

Page 3: ...durch Elektrofachkräfte zu installieren Bedienung durch jedermann ohne dem Vorkenntnisse Die Steckdose muβ nahe dem Gerät angebracht und leicht zugänglich sein Bei der Installation dieses Gerätes ist darauf zu achten daβ die Summe der Ableitstöme der USV und der angeschlossenen Verbraucher den Maximalwert von 3 5mA nicht Überschreiten Vorsicht Gefahr durch elektrischen Schlag Auch nach Trennung vo...

Page 4: ...AND UPS must be stored prior to installation storage must be in a dry place The admissible storage temperature range is 15 to 55 All handling operations will require at least two people unpacking installation in rack systems Once installed and connected to the AC power source for the first time the battery will start to charge Full charging to obtain the rated battery backup time requires at least...

Page 5: ...perator s manual for additional information such as important operating and maintenance SAFETY EARTHING TERMINAL Indicates the primary safety ground RJ 45 RECEPTACLE For 230V units only this receptacle provides network interface connections Do not plug telephone or telecommunications equipment into this receptacle This symbol indicates that you should not discard the INVERTER AND UPS AND the UPS b...

Page 6: ...Indication and Control Page 17 5 1 LED Display Page 17 5 2 LCD Display Page 17 5 3 Audible alarm Page 19 5 4 Auto self test Function Page 19 5 5 Remote Control Page 20 5 6 Reset the INVERTER AND UPS Page 20 6 Communication interface Page 21 7 Trouble shooting Page 22 8 Specifications Page 23 8 1 IS LT Long Run Series Tower 1100VA 5000VA Page 23 8 2 IS LR Long Run Series Rack 2000VA 5000VA Page 26 ...

Page 7: ...iability the unique benefits of the UPS include the following Pure sine wave output Microprocessor based design with true Line Interactive structure Adjustable voltage sensitivity charging voltage voltage transfer points Remaining Estimated Backup Time indication EBT system on LCD version Smart battery management with intelligent double stages of charging control Real time auto detection for batte...

Page 8: ...ere are many types of LED display for different models however they all use the same control method the following are two examples Front panel Example 1 Front panel Example 2 LEDs of battery voltage level and load level LED of operation status Control button 1 3 2 ...

Page 9: ...LCD series The following is one example of LCD display the location of control buttons could be different for some models however the functions of buttons are the same Main control button LCD screen Selection button for mode value 1 2 3 ...

Page 10: ...Panel 1 RS 232 Interface port 2 Outlets NEMA or IEC 3 Data line protection RJ 45 Optional 4 Inlet of city power 5 Fuse some models apply circuit breaker 6 Battery connector for Long run models only optional for Anderson s type 7 USB port Optional 8 Internal SNMP Slot Optional ...

Page 11: ... for Standard IS5000LT Rear Panel 1 RS 232 Interface port 2 Outlets IEC 3 Data line protection RJ 45 Optional 4 Input 5 Circuit breaker 6 Extended battery connector 7 USB port Optional 8 DIP switch setting Ref item 5 5 1 ...

Page 12: ... 3 Selection button for mode value 4 Main control button 5 RS 232 Interface port 6 RS 232 Interface port DB9 7 Internal SNMP Slot Optional 8 Output circuit breaker 9 AC output 10A max Rear Panel 1 Input circuit breaker 2 Input terminal 3 Output terminal 4 Cooling fan 5 External battery terminal ...

Page 13: ...ipment is not over the rated capacity of the UPS Red LED will light up LED version or the Over load symbol will show up LCD version and alarm will beep if the load is over the rated value Meantime if the overload is severe the UPS will shut down immediately for protecting UPS itself 3 4 If you are going to use the setting software i e UPS Wizard connect your computer to the communication port of U...

Page 14: ...nge every 2 seconds or LCD display will show OFF in LCD version then wait for 10 seconds and UPS will turn off the power automatically 4 4 In OFF mode UPS will turn off power completely in 10 seconds during a utility failure while UPS will keep charging the batteries if the utility power is normal When utility power is normal please pull out the power cord if you want to turn off the UPS completel...

Page 15: ...cell has a small difference of self discharge rate in a long term in which the small difference of self discharge rate will cause big difference among all the charged batteries This phenomenon may not only shorten the battery life but also cause wrong detection of Replace battery To prevent the wrong detection and to keep UPS batteries in the best condition the battery needs capacity balance disch...

Page 16: ... required voltage blinking Then push two selection buttons at the same time for next setting or leave the LCD blinking for 30 seconds to end the setting 4 11 4 To change the Auto turn on setting at the recovery of utility power The method of changing the setting is similar to that of voltage setting If you don t need Auto turn on function please select oFF To select On is for immediate auto turnin...

Page 17: ... load connected to UPS When the Gn 1 is blinking it means the green mode level is 1 of full load level The UPS will turn off the power automatically if blackout happened when load level is less than 1 of full load Push the selection button for 2 seconds at least to increase the green mode level or push to decrease the level Push two selection buttons at the same time to end the setting ...

Page 18: ...when all five LEDs are lighted in normal mode it means that the battery is fully charged The load level LEDs show the percentage of added load by the UPS s rated capacity When all five LEDs are lighted the UPS is over loaded 5 1 2 Operation status LED The status LED shows the UPS status It shows Green when the utility power is normal and shows Orange in the event of a utility outage while if the U...

Page 19: ...llowing situations 1 A turn on turn off schedule has been set using the monitoring software Refer to User s Manual 5 5 and the Readme file or Help function of the monitoring software 2 The Green Mode is enabled and the loading is under 25W default but adjustable The UPS will turn itself off automatically in 60 seconds Refer to 4 9 of User s Manual 8 Thermal alarm The temperature inside the UPS is ...

Page 20: ...ning In back up mode the alarm can be silenced by pushing the button However the warning of low battery will still sound for urging user to leave computer without any data loss Basic Indication Table STATUS ALARM REMARK LED Utility Good No Beep Green flash Utility outage No Beep Orange flash Idle mode Timer on refer to Item 5 5 No Beep Red flash Normal Utility good No Beep Green One beep every 4 s...

Page 21: ...0V Down Down 240V DIP setting is valid only when the DIP3 Down To apply the other setting on LCD display Please refer to 4 11 DIP 3 for Setting selection UP invalid for DIP setting Down valid for DIP setting DIP 4 for Green Mode setting UP Enable Down Disable DIP Switch Settings for special design of IS5000LT DIP 1 DIP 2 Charging current Up Up 25 Down Up 50 Up Down 75 Down Down 100 NOTE of Chargin...

Page 22: ... 7 Common of Pin 6 and Pin 9 Pin 9 RS 232 data Rx In 6 2 The definition and setup for DB9 optional is shown as follows Pin 2 AC Power Failure Pin 4 Common GND of Pin 2 Pin 5 Pin 5 INVERTER AND INVERTER AND UPS Battery Low Pin 6 Turn off INVERTER AND INVERTER AND UPS Pin 7 GND of Pin6 The interface with computer is diagramed as above for your reference Use Pin 4 as the common of Pin 2 and Pin 5 Pin...

Page 23: ... AND UPS does not provide expected run time 1 Excessive loads connected at INVERTER AND UPS s outlets 2 Battery is weak and cannot provide enough capacity Do not operate the INVERTER AND UPS and leave the INVERTER AND UPS plugged in for 10 hours Then test it again if INVERTER AND UPS still cannot provide expected run time battery should be replaced Button on front panel doesn t work 1 The CPU insi...

Page 24: ...Models 230V Models IS1100LT 1100VA 660W IS2200LT 2200VA 1350W IS3000LT 3000VA 1800W Power Levels crated at nominal inputs N A IS5000LT 5000VA 3200W Output Voltage 100V 110V 120V Selectable 220V 230V 240V Selectable Voltage Waveform Sine wave Crest Factor 3 1 4 5 1 optional Output Frequency Synchronized to Mains Auto Select for 50 60Hz 47Hz 55Hz for 50Hz nominal 56Hz 65Hz for 60Hz nominal Regulatio...

Page 25: ...oost 12 5 of selected nominal voltage Surge Protection IS1100LT 220 Joules IS2200LT 440 Joules IS3000LT IS5000LT 660 Joules Battery Battery type Lead Acid 25Ah 250Ah IS1100LT 1100VA 660W 24Vdc 48Vdc optional IS2200LT 2200VA 1350W 48Vdc 24 36Vdc optional IS3000LT 3000VA 1800W 72Vdc 24 36 48Vdc optional Voltage N A IS5000LT 5000VA 3200W 48Vdc Typical backup time No Limit Charging method Smart pulse ...

Page 26: ...B9 SNMP Control panel LCD or LED Selectable Audible alarm Alarm on battery Low battery Battery over voltage Alarm on abnormal operation Over load Short circuit Over heat EBT Estimation of Backup Time system Support for LCD display Green mode function Auto shutdown during blackout 1 to 14 of full load adjustable by using the remote set up software The default setting is OFF Cooling fan control Auto...

Page 27: ...ing voltage Generator compatible Automatic restart of load after INVERTER AND UPS shutdown Smart AVR function Two buck boost modes Cold start capable Audible alarm Hot swappable batteries Network manageable SNMP optional Full function of LCD display LED display optional Smart battery management Intelligent double stages of charging control Wet battery compatible Thermal control cooling fan Output ...

Page 28: ...oltage Range 20 22 for selected nominal voltage 29 33 adjustable by using the remote set up software AVR Range 2 Bucks 2 Boosts Enhanced Buck 15 of selected nominal voltage Buck mode 5 of selected nominal voltage Boost mode 5 of selected nominal voltage Enhanced Boost 12 5 of selected nominal voltage Surge Protection IS2000LR IS2700LR 440 Joules IS4000LR IS5000LR 660 Joules Battery Battery type Le...

Page 29: ...ort UPSilon2000 compatible RS232 USB port is optional Optional Interface part RJ45 Surge protection DB9 USB SNMP Control panel LCD Audible alarm Alarm on battery Low battery Battery over voltage Alarm on abnormal operation Over load Short circuit Over heat EBT Estimation of Backup Time system Yes Green mode function Auto shutdown during blackout 1 to 14 of full load adjustable by using the remote ...

Page 30: ...3x12 9x23 inch 132x447x132 584x327 7x584 mm IS5000LR 6 9x18 7x6 9 25x15 6x23 4 inch 176x475x176 635x396x594 3 mm Weight Net Gross IS2000LR IS2700LR 57 5 66 3 lbs 26 30 kg IS4000LR 75 1 84 lbs 34 38 kg IS5000LR 97 2 106 lbs 44 48 kg Packing Export carton for each unit 16 30 units per pallet ...

Page 31: ...30 www opti ups com ...