UP-67ETH, UP-127ETH,
UP-247ETH, UP-367ETH
Digital power unit
UP-x7ETH version 1.1
36
6.6. Configuration of the Automatic Level Control tab
By clicking on this tab, the parameters for the automatic level control of the amplifier in installations with
NS-485 noise sensors can be configured.
If noise sensors are not used, leave the controls on
Bypass
.
If you have noise sensors, proceed to configure the automatic level control parameters. It is necessary to
have the amplifier connected to the IP network, and the noise sensors must be connected to the amplifier
through the RS485 bus.
1. Press the button
Enter Adjust Mode (1)
.
2. Deactivate
Bypass (2)
.
3. Configure the
Measurement interval (3)
: Interval in time, in seconds, between two consecutive
measurements of the noise level (0 = continuous measurement).
4. Configure the attenuation level of the program channel during measurement
(4)
.
5. Enter the
Reverberation Time (5)
of the room or zone where measurement is performed.
6. Click on the button
Config (6)
.