background image

 

 

 

UP-67M4, UP-127M4, 
UP-247M2, UP-487 

 

Modular amplifiers. v 2.3 

Modular 

amplifiers 

(12)

 

PRIORITY CHANNEL AND (13) PROGRAM CHANNEL 

The two input channels (PROGRAM & PRIORITY) from 
each amplifier use 4 RJ45 type connectors in parallel 
2 to 2. 
This  way,  they  can  provide  signal  to  other  power 
units (see figure 9). 
For  the  connection,  you  must  use  FTP  Cat  5  cable, 
which main feature is that it has very low impedance, 
which  allows  to  have  an  exceptionally  flat  frequency 
response even for long distances, and to comply with 
the  CMRR  &  Crosstalk  features  required  for  the 
analogical audio systems. 
The  signal  inputs  have  a  sensitivity  of  0  dBu  (775 
mV). The pin number 3 provides a 24 V.d.c. voltage 
which  can  be  used  to  supply  devices  of  low 
consumption.  The  maximum  intensity  supplied  is  of 
200 mA. in each channel. 
In  the  PRIORITY  channel,  when  joining  the  pin 
number 6 to the pin number 8, the priority system is 
activated  as  well  as  the  security  paging  auxiliary 
relay (DIP switch 7 

Pri. ctrl in

 must be ON). 

It is possible to transmit the priority  control to other 
power  units  through  the  pin  nº  6  of  the  PRIORITY 
OUTPUT connector (DIP switch 8 

Pri. ctrl out

 must be 

ON). 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Figure 9 

ATTENTION: 

In  order  to  link  the  program  and  priority  audio  signals 
from  one  power  stage  to  the  other,  without  using 
external  cabling  set  the 

Pro.  audio  bus

  and 

Pri.  audio 

bus

  switch  from  AMP2,  AMP3  and  AMP4  in  ON.  In 

AMP1 they must be in OFF. 

To  link  different  mainframes,  it  can  only  be  used  the 
outputs from AMP1.

 

Figure 10 

Summary of Contents for UP-127M4

Page 1: ......

Page 2: ......

Page 3: ......

Page 4: ...Modular amplifiers v 2 3 Modular amplifiers 4 Contents 1 INTRODUCTION 5 2 FRONT VIEW 5 3 REAR VIEW 6 4 ATTENUATORS CONNECTION 11 5 ONE SECTION BLOCK DIAGRAM 12 6 TECHNICAL SPECIFICATIONS 13 7 DOCUMENT VERSION TRACKING 13 8 GUARANTEE 14 ...

Page 5: ... the power delivered to the line The LED marked as 0 dB indicated the maximum power given by the amplifier 2 PROTECTION INDICATORS They light when the Protection is operating due either to an over loading or to a short circuit in the loudspeakers line 3 PRIORITY INDICATORS They light when the Priority channel is selected it is when the pin number 6 is joined to the pin number 8 in the RJ45 connect...

Page 6: ...g with the 70 and 100V lines it should be remembered that The loudspeakers to be connected must have a line transformer The total connected power will be the sum of the power absorbed by the loudspeakers and this must be between 50 below and 20 above the rated power of the amplifier The power absorbed by a loudspeaker with a transformer is indicated on its terminals This power is on the 100 V line...

Page 7: ...he junction must be made by means of external connections as shown in figure 5 The DIP switches 1 2 3 4 SHIELD GND LINK must be OFF and the external connection must be as shown in figure 6 pin 2 must be disconnected 6 GROUND CONTACT In all P A installations it is very important to have only a joining point between the signal ground and the mains ground contact If the P A installation is made up of...

Page 8: ... line properly connected to the amplifier Note In installations with surveillance through DALA 01 0B set the JPA DIP switch to ON 10 SURVEILLANCE CONNECTION These connectors are used in installations with surveillance through SU 114N Connect the SU 114N to the power unit following the diagram shown in figure 7 11 PRIORITY CONTROL TERMINAL BLOCK These contacts allow the activation of the amplifier ...

Page 9: ...in number 3 provides a 24 V d c voltage which can be used to supply devices of low consumption The maximum intensity supplied is of 200 mA in each channel In the PRIORITY channel when joining the pin number 6 to the pin number 8 the priority system is activated as well as the security paging auxiliary relay DIP switch 7 Pri ctrl in must be ON It is possible to transmit the priority control to othe...

Page 10: ...ition it disables the priority contact of the RJ45 PRIORITY OUTPUT connector PRIORITY CONTACT SURVEILLANCE DIP switch number 9 When in ON enables the priority contact surveillance It is necessary that the activator follows the figure 12A if the priority is activated by means of RJ45 PRIORITY INPUT or 12B if the priority is activated by means of PRIORITY CTRL terminal block When the surveillance de...

Page 11: ...e Priority contact is supervised or not When ON means surveillance activated DIP switch number 9 PRIORITY CONTACT SURVEILLANCE must be ON 4 ATTENUATORS CONNECTION Figure 13 INSTALLATION WITHOUT SURETY PAGING SEGURIDAD DE AVISOS Figure 14 6 CHANNELS WITH PRIORITY AND SURETY PAGING Figure 15 1 CHANNEL WITH PRIORITY AND SURETY PAGING ...

Page 12: ...UP 67M4 UP 127M4 UP 247M2 UP 487 Modular amplifiers v 2 3 Modular amplifiers 12 5 ONE SECTION BLOCK DIAGRAM ...

Page 13: ...ion Continuous ventilation with variation according to the temperature speed Dimensions mm 482 x 360 x 133 mm Rack units 3 units Weight 23 4 kg 24 3 kg 25 3 kg 20 kg Finishing Front panel in anodised black aluminium Cover in black enamelled steel 7 DOCUMENT VERSION TRACKING Reference system Type of Document Confidentiality N A Analogue systems Installation and operation guide Rev Date Modification...

Page 14: ... the equipment including lack of maintenance 5 The guarantee shall not be valid whenever the following is observed Amendments or corrections made to the details of the guarantee certificate or purchase invoice Failure to produce the original invoice or the absence of a date on this Absence of the serial or batch number on the equipment 6 In the case of personal computers the guarantee will not cov...

Reviews: