Document No.: M00-20-6000, Rev. 02
Page 8 of 13
4. Plug the power cable into an available electrical outlet and wait for the status light of the Ethernet IP Authorization
Gateway to turn
green
and begin blinking slowly (approximately once per second).
2.4 Connecting the OPW Ethernet IP Authorization Gateway
1. Connect one of the OPW-supplied serial modem cables (20-1517-01) to the
outbound
port on the FSC.
a. On the Petro Vend System2 this is
Aux 3.
b. On the FSC3000 this is
COM 5.
Connect the other end to
POS Serial Port 1
on the OPW Ethernet IP Authorization Gateway.
2. Connect the other OPW-supplied serial modem cable (20-1517-01) to the
inbound
port on the FSC.
c. On the Petro Vend System2 this is the
Modem Port.
d. On the FSC3000 this is
COM 1.
Connect the other end to
POS Serial Port 2
on the OPW Ethernet IP Authorization Gateway.
2.5 Testing the OPW Ethernet IP Gateway for Network Authorization
1. Verify that the FSC3000 is configured properly for the processors that will be supported at the site.
NOTE
: You are configuring the FSC3000 to work in dial-out mode exactly as if you were going to use the “new” OPW
modem and a phone line.
IMPORTANT
: For all networks, except Buypass, configure the modem communication parameters to 2400 baud, 7E1 to
match the Gateway. For the Buypass network, configure the modem communication parameters to 2400 baud, 8N1 to
match the Gateway.
2. Test the connection by running a test card at the pump. You should receive a prompt stating
Select Pump
,
Enter
Pump Number
or that the
Pump is Activated
; this indicates that you have received authorization.
NOTE
: You do not need to pump fuel at this time.
2.6 Testing the OPW Ethernet IP Gateway for Inbound Communication
IMPORTANT
: The IT administrator at the site will need to configure Port Forwarding to the Static IP Address of the Ethernet
IP Authorization Gateway (Port 8002) before inbound communications will work.
Using Phoenix
®
or ARTWare, establish a connection to the fuel site controller using the static IP address assigned to the OPW
Ethernet IP Authorization Gateway.