Table 1-3 (Cont.) Environmental Requirements for Oracle Exadata Database
Machine X4-2
Environmental
Component
Oracle Exadata
Database
Machine X4-2
Full Rack
Oracle Exadata
Database
Machine X4-2
Half Rack
Oracle Exadata
Database
Machine X4-2
Quarter Rack
Oracle Exadata
Database
Machine X4-2
Eighth Rack
Cooling
See Also:
"
(page 1-44)",
and "
(page 1-45)"
•
High
performance
drives
Maximum:
41,300 BTU/
hour (43,600
kJ/hour)
Typical:
29,000 BTU/
hour (30,600
kJ/hour)
•
High
capacity
drives
Maximum:
38,300 BTU/
hour (40,400
kJ/hour)
Typical:
27,000 BTU/
hour (28,500
kJ/hour)
•
High
performance
drives
Maximum:
22,500 BTU/
hour (23,750
kJ/hour)
Typical:
16,000 BTU/
hour (16,900
kJ/hour)
•
High
capacity
drives
Maximum:
21,200 BTU/
hour (22,400
kJ/hour)
Typical:
14,700 BTU/
hour (15,500
kJ/hour)
•
High
performance
drives
Maximum:
11,300 BTU/
hour (11,900
kJ/hour)
Typical:
8,200 BTU/
hour (8,700
kJ/hour)
•
High
capacity
drives
Maximum:
10,600 BTU/
hour (11,200
kJ/hour)
Typical:
7,500 BTU/
hour (7,900
kJ/hour)
•
High
performance
drives
Maximum:
10,200 BTU/
hour (10,700
kJ/hour)
Typical:
7,100 BTU/
hour (7,500
kJ/hour)
•
High
capacity
drives
Maximum:
9,500 BTU/
hour (10,000
kJ/hour)
Typical:
6,600 BTU/
hour (7,000
kJ/hour)
Air flow front-to-
back (subject to
actual data
center
environment)
See Also:
"
(page 1-44)",
and "
(page 1-45)"
•
High
performance
drives
Maximum:
Approximatel
y 1,900 CFM
Typical:
Approximatel
y 1,350 CFM
•
High
capacity
drives
Maximum:
Approximatel
y 1,780 CFM
Typical:
Approximatel
y 1,250 CFM
•
High
performance
drives
Maximum:
Approximatel
y 1,050 CFM
Typical:
Approximatel
y 750 CFM
•
High
capacity
drives
Maximum:
Approximatel
y 980 CFM
Typical:
Approximatel
y 680 CFM
•
High
performance
drives
Maximum:
Approximatel
y 520 CFM
Typical:
Approximatel
y 365 CFM
•
High
capacity
drives
Maximum:
Approximatel
y 490 CFM
Typical:
Approximatel
y 350 CFM
•
High
performance
drives
Maximum:
Approximatel
y 470 CFM
Typical:
Approximatel
y 325 CFM
•
High
capacity
drives
Maximum:
Approximatel
y 440 CFM
Typical:
Approximatel
y 310 CFM
Chapter 1
General Environmental Requirements
1-7