Table 1-4 (Cont.) Environmental Requirements for Oracle Exadata Database
Machine X4-8 Racks with Exadata Storage Server X5-2 Servers
Environmental Component
Oracle Exadata Database
Machine X4-8 Full Rack with
Exadata Storage Server
X5-2 Servers
Oracle Exadata Database
Machine X4-8 Half Rack
with Exadata Storage
Server X5-2 Servers
Network drops
See Also: "
Connection and IP Address
Requirements for Oracle
Exadata Database Machine
(page 1-47)"
Minimum of 5 network drops
Minimum of 5 network drops
External connectivity
See Also: "
Connection and IP Address
Requirements for Oracle
Exadata Database Machine
(page 1-47)"
16 x 1 GbE Ethernet ports
16 x 10 GbE Ethernet SFP+
ports
At least 12 InfiniBand ports
16 x 1 GbE Ethernet ports
16 x 10 GbE Ethernet SFP+
ports
At least 12 InfiniBand ports
1.1.6 General Environmental Requirements for Oracle Exadata
Database Machine X4-8 Full Rack
(page 1-10) shows the general environmental requirements for Oracle
Exadata Database Machine X4-8 Full Rack. The other sections in this chapter provide
detailed information.
Table 1-5 Environmental Requirements for Oracle Exadata Database Machine
X4-8 Full Rack
Environmental Component
Oracle Exadata Database Machine X4-8
Full Rack
Weight
See Also: "
(page 1-34)"
867.3 kg (1912 lbs)
Acoustic levels
93 db(A)
Power
See Also: "
(page 1-34)"
•
High performance drives
Maximum: 15.3 kVA
Typical: 10.7 kVA (varies based on
application load)
•
High capacity drives
Maximum: 14.7 kVA
Typical: 10.3 kVA (varies based on
application load)
Chapter 1
General Environmental Requirements
1-10