Table 5-5 Threshold Values for Oracle Exadata Database Machine X4-2 Half
Rack with Single-phase, Low-voltage PDU
PDU
Module/Phase
Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A
Module 1, phase
1
0
20
24
A
Module 1, phase
2
0
10
13
A
Module 1, phase
3
0
0.1
0.2
B
Module 1, phase
1
0
0.1
0.2
B
Module 1, phase
2
0
10
13
B
Module 1, phase
3
0
20
24
(page 5-23) lists the threshold values for Oracle Exadata Database
Machine X4-2 Half Rack using a three-phase, low-voltage PDU.
Table 5-6 Threshold Values for Oracle Exadata Database Machine X4-2 Half
Rack with Three-phase, Low-voltage PDU
PDU
Module/Phase
Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A and B
Module 1, phase
1
0
17
22
A and B
Module 1, phase
2
0
19
24
A and B
Module 1, phase
3
0
15
20
(page 5-23) lists the threshold values for Oracle Exadata Database
Machine X4-2 Half Rack using a single-phase, high-voltage PDU.
Table 5-7 Threshold Values for Oracle Exadata Database Machine X4-2 Half
Rack with Single-phase, High-voltage PDU
PDU
Module/Phase
Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A
Module 1, phase
1
0
18
23
A
Module 1, phase
2
0
9
12
A
Module 1, phase
3
0
0.1
0.2
Chapter 5
Configuring the Power Distribution Units
5-23