5.3.1.5.3 PDU Thresholds for Oracle Exadata Database Machine X2-2 (with X4170 and
X4275 servers) Quarter Rack
The following tables list the threshold values for Oracle Exadata Database Machine
Quarter Rack:
•
(page 5-43)
Threshold Values for Oracle Exadata Database Machine X2-2 (with X4170 and
X4275 servers) Quarter Rack with Single-phase, Low-voltage PDU
•
(page 5-44)
Threshold Values for Oracle Exadata Database Machine X2-2 (with X4170 and
X4275 servers) Quarter Rack with Three-phase, Low-voltage PDU
•
(page 5-44)
Threshold Values for Oracle Exadata Database Machine X2-2 (with X4170 and
X4275 servers) Quarter Rack with Single-phase, High-voltage PDU
•
(page 5-44)
Threshold Values for Oracle Exadata Database Machine X2-2 (with X4170 and
X4275 servers) Quarter Rack with Three-phase, High-voltage PDU
(page 5-43) lists the threshold values for Oracle Exadata Database
Machine Quarter Rack using a single-phase, low-voltage PDU.
Table 5-45 Threshold Values for Oracle Exadata Database Machine X2-2 (with
X4170 and X4275 servers) Quarter Rack with Single-phase, Low-voltage PDU
PDU
Module/Phase
Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A
Module 1, phase
1
0
12
15
A
Module 1, phase
2
0
6
8
A
Module 1, phase
3
0
0
0
B
Module 1, phase
1
0
0
0
B
Module 1, phase
2
0
6
8
B
Module 1, phase
3
0
12
15
(page 5-44) lists the threshold values for Oracle Exadata Database
Machine Quarter Rack using a three-phase, low-voltage PDU.
Chapter 5
Configuring the Power Distribution Units
5-43