(page 5-49) lists the threshold values for Oracle Exadata Database
Machine X2-8 Full Rack using a three-phase, high-voltage 24 kVA PDU.
Table 5-56 Threshold Values for Oracle Exadata Database Machine X2-8 Full
Rack with Three-phase, High-voltage 24 kVA PDU
PDU
Module/Phase
Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A and B
Module 1, phase
1
0
18
21
A and B
Module 1, phase
2
0
18
21
A and B
Module 1, phase
3
0
17
21
5.3.1.9 PDU Thresholds for Oracle Exadata Storage Expansion Rack with
Exadata Storage Server with Sun Fire X4270 M2 Servers
This section contains the PDU thresholds for Oracle Exadata Storage Expansion Rack
with Exadata Storage Server with Sun Fire X4270 M2 Servers.
5.3.1.9.1 PDU Thresholds for Oracle Exadata Storage Expansion Full Rack with Exadata
Storage Server with Sun Fire X4270 M2 Servers
The following tables list the threshold values for Oracle Exadata Storage Expansion
Full Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers Full Rack:
•
(page 5-50) Threshold Values for Oracle Exadata Storage Expansion
Full Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers with
Single-phase, Low-voltage PDU
•
(page 5-50) Threshold Values for Oracle Exadata Storage Expansion
Full Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers with
Three-phase, Low-voltage PDU
•
(page 5-50) Threshold Values for Oracle Exadata Storage Expansion
Full Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers with
Single-phase, High-voltage PDU
•
(page 5-51) Threshold Values for Oracle Exadata Storage Expansion
Full Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers with
Three-phase, High-voltage PDU
(page 5-50) lists the threshold values for Oracle Exadata Storage
Expansion Full Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers
using a single-phase, low-voltage PDU.
Chapter 5
Configuring the Power Distribution Units
5-49