Table 5-57 Threshold Values for Oracle Exadata Storage Expansion Full Rack
with Exadata Storage Server with Sun Fire X4270 M2 Servers with Single-phase,
Low-voltage PDU
PDU
Module/Phase
Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A
Module 1, phase
1
0
18
23
A
Module 1, phase
2
0
22
24
A
Module 1, phase
3
0
18
23
B
Module 1, phase
1
0
18
23
B
Module 1, phase
2
0
22
24
B
Module 1, phase
3
0
18
23
(page 5-50) lists the threshold values for Oracle Exadata Storage
Expansion Full Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers
using a three-phase, low-voltage PDU.
Table 5-58 Threshold Values for Oracle Exadata Storage Expansion Full Rack
with Exadata Storage Server with Sun Fire X4270 M2 Servers with Three-phase,
Low-voltage PDU
PDU
Module/Phase
Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A and B
Module 1, phase
1
0
32
40
A and B
Module 1, phase
2
0
34
43
A and B
Module 1, phase
3
0
33
42
(page 5-50) lists the threshold values for Oracle Exadata Storage
Expansion Full Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers
using a single-phase, high-voltage PDU.
Table 5-59 Threshold Values for Oracle Exadata Storage Expansion Full Rack
with Exadata Storage Server with Sun Fire X4270 M2 Servers with Single-phase,
High-voltage PDU
PDU
Module/Phase
Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A
Module 1, phase
1
0
16
20
Chapter 5
Configuring the Power Distribution Units
5-50