Table 1-28 Low-voltage 22 kVA Single Phase PDUs for North America, South
America, Japan and Taiwan (2 PDUs per Rack)
Option
Requirement, per PDU
Voltage
200 - 240 VAC
Frequency
50/60 Hz
Current
36.8 A maximum per input / 110.4 A Maximum
per PDU
Power rating
22 kVA
Output current
110.4A (3x 36.8)
Outlets
42 x C13; 6 x C19
Outlet groups
6
Group protection (UL489 2-pole circuit
breaker)
20A
Data center receptacle
Hubbell CS8265C
The following are needed to connect an Oracle Exadata system to a low-voltage
single-phase power source:
•
3 power cords for two PDUs
•
6 receptacles to connect the PDUs
(page 1-39) shows the low-voltage, 22 kVA single phase PDU power
connector for North America, South America, Japan and Taiwan. This power
connector is different from the power connector for the low-voltage 15 kVA single
phase PDU.
Figure 1-5 Low-voltage 22 kVA Single Phase Power Connector
(page 1-39) lists the requirements for 22 kVA high-voltage one-phase
PDUs for Europe, the Middle East, Africa, and Asia Pacific, except Japan and Taiwan.
There are two PDUs per rack. The following specifications are per PDU.
Table 1-29 High-voltage 22 kVA Single Phase PDUs for Europe, the Middle East
and Africa (EMEA), and Asia Pacific (APAC), except for Japan and Taiwan (2
PDUs per Rack)
Option
Requirement, per PDU
Voltage
220-240 VAC