Table 1-2 (Cont.) Environmental Requirements for Oracle Exadata Database
Machine X5-8
Environmental Component
Oracle Exadata Database
Machine X5-8 Full Rack
Oracle Exadata Database
Machine X5-8 Half Rack
Power
See Also: "
(page 1-34)"
Extreme Flash drives:
•
Max: 16.4 kW (16.7 kVA)
•
Typical: 11.5 kW (11.7
kVA)
High capacity drives:
•
Max: 16.2 kW (16.6 kVA)
•
Typical: 11.4 kW (11.6
kVA)
Extreme Flash drives:
•
Max: 9.5 kW (9.7 kVA)
•
Typical: 6.7 kW (6.8 kVA)
High capacity drives:
•
Max: 9.5 kW (9.7 kVA)
•
Typical: 6.6 kW (6.8 kVA)
Cooling
See Also: "
(page 1-44)", and
"
(page 1-45)"
Extreme Flash drives:
•
Max: 55,935 BTU/hour
(59,012 kJ/hour)
•
Typical: 39,155 BTU/hour
(41,308 kJ/hour)
High capacity drives:
•
Max: 55,410 BTU/hour
(58,457 kJ/hour)
•
Typical: 38,787 BTU/hour
(40,920 kJ/hour)
Extreme Flash drives:
•
Max: 32,436 BTU/hour
(34,220 kJ/hour)
•
Typical: 22,705 BTU/hour
(23,954 kJ/hour)
High capacity drives:
•
Max: 32,323 BTU/hour
(34,101 kJ/hour)
•
Typical: 22,626 BTU/hour
(23,871 kJ/hour)
Air flow front-to-back (subject
to actual data center
environment)
See Also: "
(page 1-44)", and
"
(page 1-45)"
Extreme Flash drives:
•
Max: 2590 CFM
•
Typical: 1813 CFM
High capacity drives:
•
Max: 2565 CFM
•
Typical: 1796 CFM
Extreme Flash drives:
•
Max: 1502 CFM
•
Typical: 1051 CFM
High capacity drives:
•
Max: 1496 CFM
•
Typical: 1048 CFM
1.1.4 General Environmental Requirements for Oracle Exadata
Database Machine X4-2
The environmental requirements for Oracle Exadata Database Machine X4-2 depend
on the size of the system.
(page 1-6) shows the general environmental
requirements for Oracle Exadata Database Machine X4-2. The other sections in this
chapter provide detailed information.