Note:
The values listed here are reliable for use on systems in the configuration
received upon deployment and delivery from the Oracle Factory. Any changes
to this configuration should be modeled in Oracle Exadata Configuration
Assistant (OECA), and the PDU thresholds listed in OECA should then be
used. OECA can be downloaded from Oracle Technology Network.
5.3.1.5.1 PDU Thresholds for Oracle Exadata Database Machine X2-2 (with X4170 and
X4275 servers) Full Rack
The following tables list the threshold values for Oracle Exadata Database Machine
X2-2 (with X4170 and X4275 servers) Full Rack:
•
(page 5-39) Threshold Values for Oracle Exadata Database Machine
X2-2 (with X4170 and X4275 servers) Full Rack with Single-phase, Low-voltage
PDU
•
(page 5-40) Threshold Values for Oracle Exadata Database Machine
X2-2 (with X4170 and X4275 servers) Full Rack with Three-phase, Low-voltage
PDU
•
(page 5-40) Threshold Values for Oracle Exadata Database Machine
X2-2 (with X4170 and X4275 servers) Full Rack with Single-phase, High-voltage
PDU
•
(page 5-40) Threshold Values for Oracle Exadata Database Machine
X2-2 (with X4170 and X4275 servers) Full Rack with Three-phase, High-voltage
PDU
(page 5-39) lists the threshold values for Oracle Exadata Database
Machine Full Rack using a single-phase, low-voltage PDU.
Table 5-37 Threshold Values for Oracle Exadata Database Machine X2-2 (with
X4170 and X4275 servers) Full Rack with Single-phase, Low-voltage PDU
PDU
Module/Phase
Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A
Module 1, phase
1
0
22
24
A
Module 1, phase
2
0
22
24
A
Module 1, phase
3
0
21
24
B
Module 1, phase
1
0
21
24
B
Module 1, phase
2
0
22
24
B
Module 1, phase
3
0
22
24
Chapter 5
Configuring the Power Distribution Units
5-39