(page 5-40) lists the threshold values for Oracle Exadata Database
Machine Full Rack using a three-phase, low-voltage PDU.
Table 5-38 Threshold Values for Oracle Exadata Database Machine X2-2 (with
X4170 and X4275 servers) Full Rack with Three-phase, Low-voltage PDU
PDU
Module/Phase
Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A and B
Module 1, phase
1
0
36
45
A and B
Module 1, phase
2
0
39
44
A and B
Module 1, phase
3
0
38
45
(page 5-40) lists the threshold values for Oracle Exadata Database
Machine Full Rack using a single-phase, high-voltage PDU.
Table 5-39 Threshold Values for Oracle Exadata Database Machine X2-2 (with
X4170 and X4275 servers) Full Rack with Single-phase, High-voltage PDU
PDU
Module/Phase
Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A
Module 1, phase
1
0
20
21
A
Module 1, phase
2
0
20
21
A
Module 1, phase
3
0
19
21
B
Module 1, phase
1
0
19
21
B
Module 1, phase
2
0
20
21
B
Module 1, phase
3
0
20
21
(page 5-40) lists the threshold values for Oracle Exadata Database
Machine Full Rack using a three-phase, high-voltage PDU.
Table 5-40 Threshold Values for Oracle Exadata Database Machine X2-2 (with
X4170 and X4275 servers) Full Rack with Three-phase, High-voltage PDU
PDU
Module/Phase
Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A and B
Module 1, phase
1
0
20
21
A and B
Module 1, phase
2
0
21
21
A and B
Module 1, phase
3
0
18
21
Chapter 5
Configuring the Power Distribution Units