Table 5-59 (Cont.) Threshold Values for Oracle Exadata Storage Expansion Full
Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers with Single-
phase, High-voltage PDU
PDU
Module/Phase
Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A
Module 1, phase
2
0
20
21
A
Module 1, phase
3
0
16
20
B
Module 1, phase
1
0
16
20
B
Module 1, phase
2
0
20
21
B
Module 1, phase
3
0
16
20
(page 5-51) lists the threshold values for Oracle Exadata Storage
Expansion Full Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers
using a three-phase, high-voltage PDU.
Table 5-60 Threshold Values for Oracle Exadata Storage Expansion Full Rack
with Exadata Storage Server with Sun Fire X4270 M2 Servers with Three-phase,
High-voltage PDU
PDU
Module/Phase
Info Low
Threshold
Pre Warning
Threshold
Alarm
Threshold
A and B
Module 1, phase
1
0
18
21
A and B
Module 1, phase
2
0
18
21
A and B
Module 1, phase
3
0
17
21
5.3.1.9.2 PDU Thresholds for Oracle Exadata Storage Expansion Half Rack with Exadata
Storage Server with Sun Fire X4270 M2 Servers
The following tables list the threshold values for Oracle Exadata Storage Expansion
Half Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers:
•
(page 5-52) Threshold Values for Oracle Exadata Storage Expansion
Half Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers with
Single-phase, Low-voltage PDU
•
(page 5-52) Threshold Values for Oracle Exadata Storage Expansion
Half Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers with
Three-phase, Low-voltage PDU
•
(page 5-53) Threshold Values for Oracle Exadata Storage Expansion
Half Rack with Exadata Storage Server with Sun Fire X4270 M2 Servers with
Single-phase, High-voltage PDU
Chapter 5
Configuring the Power Distribution Units
5-51