Acoustic Noise Emissions
Specification
Operating
Nonoperating
Ambient temperature
†
Maximum: 5°C to 35°C (41°F to 113°F) up to 1829 meters
(6000 feet)
‡
Optimal: 21°C to 23˚C (69.8°F to 73.4°F)
Short-term maximum: -5°C to 55°C (23°F to 131°F)
−40°C to 70°C (−40°F to 158°F)
Relative humidity
5% to 85% RH, noncondensing, not to exceed 0.024 kg water/
kg dry air (0.053 lb. water/2.205 lbs. dry air)
Short-term: 5% to 90% RH, noncondensing, not to exceed 0.024
kg of water per kg of dry air (0.053 lb. water/2.205 lbs. dry air)
93%, non condensing, 40°C (104°F)
maximum wet bulb
Elevation (company
requirement)
Maximum 3000 meters (9840 feet) at 40°C (104°F)
Maximum 12,000 meters (39,370 feet)
Elevation (NEBS requirement) -60 meters to 1800 meters (-200 feet to 5905 feet) at 40°C (104°
F)
1800 meters to 4000 meters (5905 feet to 13,123 feet) at 30°C
(86°F)
Up to 12,000 meters (39,370 feet)
†
Does not apply to removable media devices.
‡
Maximum ambient operating temperature is derated by 1°C per 500m elevation.
Related Information
■
“Physical Specifications” on page 17
■
“Electrical Specifications” on page 18
■
“Input Power Information” on page 19
■
“DC Power Source, Power Connection, and Grounding Requirements” on page 21
■
“Overcurrent Protection Requirements” on page 20
■
“Acoustic Noise Emissions” on page 23
■
“Airflow Precautions” on page 24
Acoustic Noise Emissions
The declared noise emissions for the server are in accordance with ISO 9296 standards.
Parameter
Operating Noise Emissions
Acoustic sound power LwA (dBA)
75 dBA (AC server)
75 dBA (DC server)
Confirming Specifications
23
Summary of Contents for Netra SPARC S7-2
Page 1: ...Netra SPARC S7 2 Server Installation Guide Part No E73206 03 January 2017 ...
Page 2: ......
Page 8: ...8 Netra SPARC S7 2 Server Installation Guide January 2017 ...
Page 10: ...10 Netra SPARC S7 2 Server Installation Guide January 2017 ...
Page 26: ...26 Netra SPARC S7 2 Server Installation Guide January 2017 ...
Page 60: ...60 Netra SPARC S7 2 Server Installation Guide January 2017 ...
Page 96: ...96 Netra SPARC S7 2 Server Installation Guide January 2017 ...
Page 102: ...102 Netra SPARC S7 2 Server Installation Guide January 2017 ...