Disconnect Power Cords and Data Cables
■
“Power Off the Server (Oracle ILOM)” on page 68
■
“Power Off the Server (Power Button - Graceful)” on page 69
Disconnect Power Cords and Data Cables
1.
Power off the server.
See:
■
“Power Off the Server (Oracle ILOM)” on page 68
■
“Power Off the Server (Power Button - Graceful)” on page 69
■
“Power Off the Server (Emergency Shutdown)” on page 69
2.
Unplug all power cords from the server.
Caution -
Because 3.3 VDC standby power is always present in the system, you must unplug
the power cords before accessing any cold-serviceable components.
■
For AC power cords.
■
For DC power cords.
70
Netra Server X5-2 Service Manual • October 2016
Summary of Contents for netra X5-2
Page 1: ...Netra Server X5 2 Service Manual Part No E53601 03 October 2016 ...
Page 2: ......
Page 12: ...12 Netra Server X5 2 Service Manual October 2016 ...
Page 20: ...20 Netra Server X5 2 Service Manual October 2016 ...
Page 59: ...Using the Server Fault Remind Button Detecting and Managing Faults 59 ...
Page 60: ...60 Netra Server X5 2 Service Manual October 2016 ...
Page 128: ...128 Netra Server X5 2 Service Manual October 2016 ...
Page 144: ...144 Netra Server X5 2 Service Manual October 2016 ...
Page 148: ...148 Netra Server X5 2 Service Manual October 2016 ...
Page 154: ...154 Netra Server X5 2 Service Manual October 2016 ...
Page 180: ...180 Netra Server X5 2 Service Manual October 2016 ...
Page 210: ...210 Netra Server X5 2 Service Manual October 2016 ...
Page 226: ...226 Netra Server X5 2 Service Manual October 2016 ...
Page 266: ...266 Netra Server X5 2 Service Manual October 2016 ...
Page 274: ...274 Netra Server X5 2 Service Manual October 2016 ...