Verify a Fan Module
Verify a Fan Module
After you install a fan module, you can verify its functionality.
1.
Access Oracle ILOM.
See
“Access the SP (Oracle ILOM)” on page 28
.
2.
Reset the fan module.
->
set /SYS/MB/FM
x
clear_fault_action=true
Are you sure you want to clear /SYS/MB/FM0 (y/n)?
y
Set 'clear_fault_action' to 'true'
->
where
x
is the fan module,
0
(left fan module) to
4
(right fan module).
3.
Verify that the fan module is no longer considered faulty, then return to this
procedure.
See
“Locate a Faulty Fan Module” on page 131
4.
Verify the fan module speeds.
->
show /SYS/MB/FM
x
/F
y
/TACH value
/SYS/MB/FM0/F0/TACH
Properties:
value = 3100.000 RPM
->
where:
■
x
is the fan module,
0
(left fan module) to
4
(right fan module).
■
y
is the fan element,
0
(primary) or
1
(secondary).
Related Information
■
“Install a Fan Module” on page 133
■
■
“Locate a Faulty Fan Module” on page 131
136
Netra Server X5-2 Service Manual • October 2016
Summary of Contents for netra X5-2
Page 1: ...Netra Server X5 2 Service Manual Part No E53601 03 October 2016 ...
Page 2: ......
Page 12: ...12 Netra Server X5 2 Service Manual October 2016 ...
Page 20: ...20 Netra Server X5 2 Service Manual October 2016 ...
Page 59: ...Using the Server Fault Remind Button Detecting and Managing Faults 59 ...
Page 60: ...60 Netra Server X5 2 Service Manual October 2016 ...
Page 128: ...128 Netra Server X5 2 Service Manual October 2016 ...
Page 144: ...144 Netra Server X5 2 Service Manual October 2016 ...
Page 148: ...148 Netra Server X5 2 Service Manual October 2016 ...
Page 154: ...154 Netra Server X5 2 Service Manual October 2016 ...
Page 180: ...180 Netra Server X5 2 Service Manual October 2016 ...
Page 210: ...210 Netra Server X5 2 Service Manual October 2016 ...
Page 226: ...226 Netra Server X5 2 Service Manual October 2016 ...
Page 266: ...266 Netra Server X5 2 Service Manual October 2016 ...
Page 274: ...274 Netra Server X5 2 Service Manual October 2016 ...