Preparing the Site
3
Environmental Requirements
Acoustic Noise Emissions
Electrical Specifications
Related Information
■
“Power Cord Requirements” on page 8
■
“Attach the Power Cords” on page 78
Parameter
Operating
Ambient temperature
41˚F to 95˚F (5˚C to 35˚C)
Relative humidity
5% to 90% noncondensing, 80˚F (27˚C) maximum wet bulb
Elevation (Sun requirement)
Maximum 9840 feet (3000 meters) at 104˚F (40˚C)
Parameter
Operating
Idling
Acoustic power LWAd (1B=10dB)
7.1 B
7.2 B
Acoustic pressure LpAm
58.9 dBA
59.0 dBA
Parameter
AC Version Requirement
Voltage
200 VAC to 240 VAC single phase, 47-63 Hz
Current (per input)
20 A maximum per input at 200 VAC
Current (total)
32 A maximum total for all inputs at 200 VAC
Power
6400 Watt (Total input power is approximately equally
divided among the operating power supplies)
2900 Watt maximum per power supply