5.2 Replacing a Power Supply
132
Sun Netra T5440 Server • September 2015
5.2
Replacing a Power Supply
The server's redundant hot-swappable power supplies enable you to remove and install a power
supply without shutting the server down provided that at least to other power supplies are
operating.
The following LEDs are lit when a power supply fault is detected:
■
Front and rear Service Required LEDs.
■
Amber Failure LED on the faulty power supply
If a power supply fails and you do not have a replacement available, leave the failed power
supply installed to ensure proper air flow in the server.
Remove a Power Supply
1.
Identify which power supply requires replacement.
Power supplies from left to right: PS 0, PS 1, PS 2, PS 3.
A lit (amber) Fault LED on a power supply indicates that a failure was detected. See
.
2.
Disconnect the power cord from the faulty power supply.
3.
Grasp the power supply handle and push the power supply latch to the left while
pushing inward on the power supply (
).
4.
Pull the power supply out of the chassis (
).