18
Sun Network QDR InfiniBand Gateway Switch Service Manual for Firmware Version 2.1 • March 2013
Related Information
■
“Interpreting Status LEDs” on page 1
■
“Managing Faulty Components” on page 7
■
“Identify Faults in the Oracle ILOM Event Log” on page 12
■
“Determining the Alarm State of a Component or System” on page 13
■
“Accessing CLI Prompts” on page 34
▼
Display Oracle ILOM Sensor Status
1. Access the Oracle ILOM CLI.
See
“Access the Oracle ILOM CLI (NET MGT Port)” on page 35
.
2. Type.
Step
Description
Links
1.
Identify a suspect sensor and display its
value.
“Display Oracle ILOM Sensor Status” on page 18
2.
Determine the sensor target and alarm
type.
“Determine Oracle ILOM Sensor Target Types” on
page 20
3.
Evaluate the sensor type alarm.
“Evaluating a Voltage Sensor Alarm” on page 20
“Evaluating a Temperature Sensor Alarm” on page 23
“Evaluating a Speed Sensor Alarm” on page 26
“Evaluating a State Sensor Alarm” on page 29
“Evaluating a Presence Sensor Alarm” on page 30
“Evaluating an Indicator State” on page 32
->
show / -a -l 4 -o table alarm_status
Target | Property | Value
--------------------+------------------------+----------
/SYS/MB/V_ECB | alarm_status | cleared
/SYS/MB/V_3.3VMain | alarm_status | cleared
/SYS/MB/ | alarm_status | cleared
V_3.3VMainOK | |
/SYS/MB/V_3.3VStby | alarm_status | minor
.
.
.
/SYS/FAN3/PRSNT | alarm_status | cleared