Preparing for Cooling
■
“Perforated Floor Tiles” on page 110
Environmental Requirements
Condition
Operating Requirement
Non-operating Requirement
Comments
Temperature
5 to 32°C (41 to 89.6°F)
-40 to 70°C (-40 to 158°F).
For optimal rack cooling, data
center temperatures from 21 to
23°C (70 to 47°F)
Relative humidity
10 to 90% relative humidity,
noncondensing
Up to 93% relative humidity.
For optimal data center
rack cooling, 45 to 50%,
noncondensing
Altitude
3048 m (10000 ft.) maximum
†
12000 m (40000 ft.).
Ambient temperature is de-rated
by 1 degree Celsius per 300 m
above 900 m altitude above sea
level
†
Except in China where regulations may limit installations to a maximum altitude of 2000 m (6560 ft.).
Related Information
■
“Heat Dissipation and Airflow Requirements” on page 107
■
“Perforated Floor Tiles” on page 110
Heat Dissipation and Airflow Requirements
The following table lists the maximum rate of heat released from a system. In order to cool the
system properly, ensure that adequate airflow travels through the system.
TABLE 17
SuperCluster T5-8 Specifications
Comments
Full Rack
Half Rack
Maximum
54,405 BTU/hour
31,013 BTU/hour
57.4 kJ/hour
32.69 kJ/hour
Typical
45,422 BTU/hour
25,591 BTU/hour
47.8 kJ/hour
26.97 kJ/hour
TABLE 18
Exadata X5-2 Expansion Rack Specifications
Configuration
BTU/Hour
kj/Hour
EF Quarter rack
Maximum
12,362
13,042
Preparing the Site
107
Summary of Contents for SuperCluster T5-8
Page 1: ...Oracle SuperCluster T5 8 Owner s Guide Part No E40167 17 May 2016 ...
Page 2: ......
Page 11: ...Contents Index 353 11 ...
Page 12: ...12 Oracle SuperCluster T5 8 Owner s Guide May 2016 ...
Page 14: ...14 Oracle SuperCluster T5 8 Owner s Guide May 2016 ...
Page 116: ...116 Oracle SuperCluster T5 8 Owner s Guide May 2016 ...
Page 204: ...204 Oracle SuperCluster T5 8 Owner s Guide May 2016 ...
Page 228: ...228 Oracle SuperCluster T5 8 Owner s Guide May 2016 ...
Page 244: ...244 Oracle SuperCluster T5 8 Owner s Guide May 2016 ...