ZFS Storage Appliance Connections
ZFS Storage Appliance Connections
These connections are for these major components:
■
ZFS storage controller No. 1 (U33)
■
ZFS storage controller No. 2 (U34)
■
Sun Disk Shelf (U28)
From Storage
Controller Slot
Storage Controller Port
To Slot
To Port
Cable
U33
PCIE-1 P0
U34
PCIE-1 P2
Yellow, 7 ft.
U33
PCIE-1 P1
U34
PCIE-1 P1
Black, 7 ft.
U33
PCIE-1 P2
U34
PCIE-1 P0
Green, 7 ft.
U34
PCIE-2 P1
U28
IOM0 P0
Black, 2 m
U33
PCIE-2 P1
U28
IOM0 P2
Black, 2 m
U34
PCIE-2 P0
U28
IOM1 P0
Black, 2 m
U33
PCIE-2 P0
U28
IOM1 P2
Black, 2 m
Single-Phase PDU Cabling
If the rack uses single-phase AC power, connect the devices in the rack to the power
distribution unit (PDU) as shown in the following table. Each device requires two power cords
for redundant power.
Caution -
Turn off all PDU circuit breakers before connecting power cords to the PDU. Every
socket group has a circuit breaker.
See
Figure 31, “Circuit Breakers and AC Sockets on the PDU,” on page 252
of the PDU circuit breakers and for names of the PDU AC sockets.
Slot
PDU-A/PSU-0
(T5-8 AC0)
PDU-B/PSU-0
(T5-8 AC2)
PDU-A/PSU-1
(T5-8 AC1)
PDU-B/PSU-1
(T5-8 AC3)
To Device
U41
Group 5-6
Group 0-0
—
—
Exadata Storage Server No. 8 (Full
Rack)
U39
Group 5-5
Group 0-1
—
—
Exadata Storage Server No. 7 (Full
Rack)
U37
Group 5-4
Group 0-2
—
—
Exadata Storage Server No. 6 (Full
Rack)
258
Oracle SuperCluster T5-8 Owner's Guide • May 2016
Summary of Contents for SuperCluster T5-8
Page 1: ...Oracle SuperCluster T5 8 Owner s Guide Part No E40167 17 May 2016 ...
Page 2: ......
Page 11: ...Contents Index 353 11 ...
Page 12: ...12 Oracle SuperCluster T5 8 Owner s Guide May 2016 ...
Page 14: ...14 Oracle SuperCluster T5 8 Owner s Guide May 2016 ...
Page 116: ...116 Oracle SuperCluster T5 8 Owner s Guide May 2016 ...
Page 204: ...204 Oracle SuperCluster T5 8 Owner s Guide May 2016 ...
Page 228: ...228 Oracle SuperCluster T5 8 Owner s Guide May 2016 ...
Page 244: ...244 Oracle SuperCluster T5 8 Owner s Guide May 2016 ...